1200V 2P T2 Remote Signaling Surge Protection Device - 20-40kA China Suppliers & Factory for PV Systems
Model Meaning
Product principle and working conditions
- Meets ClassⅡ (8/20μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20μs 40kA
- No power frequency continuous flow
- The operating environment temperature is -40°C~+80°C
- Remote signaling function is optional.
- When product falls, the green window turns to red and remote signaling provides remote alarm function
Technical parameter details
| POLE | 2P/2+0 | ||||
| Technology | MOV(Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE/N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220v | 300V | 380V | 400V | 225V |
| Max.continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current(8/20μs) [In] | 20kA | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | ||||
| Temporary overvoltage(TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [lsccr] | 25kA | ||||
| Max, backup fuse | 63AgL/Gg | ||||
Mechanical Data
| Mechanical Data | ||||
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DlN rail | |||
| Housing material | Thermoplastic,UL 94 V-O | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A;125V/0.2A;75V/0.5A | |||
| Certification | CE,CB,RoHS,TUV | |||
Outer appearance and installation dimensions
Installation considerations
- Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
- It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
- Follow the installation diagram for connection during installation. DC+ is the positive pole, DC- is the negative pole, and PE is the ground wire. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
- After installation, insert the module into place and verify if the surge protection module is functioning correctly.
- During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
- Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions
What is the operating temperature range for this surge protection device?
The operating environment temperature for this device ranges from -40°C to +80°C, making it suitable for extreme weather conditions.
How do I know if the surge protection module has failed or needs replacement?
The device features a status window. Under normal operation, the window is green. If the module malfunctions or fails, the window turns red, and the optional remote signaling terminal can trigger an external alarm.
What kind of technology does this surge protection module employ?
It is built on advanced zinc oxide technology and utilizes a 34S MOV (Metal Oxide Varistor) combined with GDT (Gas Discharge Tube) to deliver maximum protection without power frequency continuous flow.
What is the maximum discharge current (Imax) for this device?
The maximum discharge current (8/20μs) [Imax] of this surge protection device is up to 40kA, providing robust protection against high-energy surges.
What are the key wiring requirements during installation?
Always disconnect the power before installation. The parallel-connected power modules must be wired strictly according to the diagram (DC+ for positive, DC- for negative, and PE for ground). Keep the connection wires secure, short, thick, and straight.
Is remote signaling supported on this model?
Yes, the remote signaling function is optional. It provides a remote alarm signal when the surge protection module requires maintenance or replacement.