1500V 3P Type 2 Surge Protection Device for Air Conditioners | China Suppliers & Factory - LKX-PV
01
Model Meaning
02
Product principle and working conditions
- Meets ClassⅡ (8/20μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20μs 40kA
- No power frequency continuous flow
- The operating environment temperature is -40°C~+80°C
- Remote signaling function is optional.
- When product falls, the green window turns to red and remote signaling provides remote alarm function
03
Technical parameter details
| Technical Data | ||||
|---|---|---|---|---|
| POLE | 3P | |||
| SPD Type | Type 2/ClassⅡ | |||
| Technology | MOV/MOV+GDT | |||
| Protection mode(s) | DC+PE.DC | |||
| Max.continuous operating voltage (D.c.) [Ucpv] | 800V | 1000V | 1200V | 1500V |
| Nominal discharge current(8/20μs) [In] | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | |||
| Protection level [Up] | ≤3.6kV | ≤4.0kV | ≤4.5kV | ≤5.2kV |
| Response time [tA] | ≤25ns | |||
| Admissible short-circuit current [lsccr] | 25kA | |||
| Max, backup fuse | 125AgL/Gg | |||
04
Mechanical Data
| Mechanical Data | ||||
|---|---|---|---|---|
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DIN rail | |||
| Housing material | Thermoplastic,UL 94 V-O | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A;125V/0.2A;75V/0.5A | |||
| Certification | CE,CB,RoHS,TUV | |||
05
Outer appearance and installation dimensions
06
Installation considerations
- 1 Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
- 2 It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
- 3 Follow the installation diagram for connection during installation. DC+ is the positive pole, DC- is the negative pole, and PE is the ground wire. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
- 4 After installation, insert the module into place and verify if the surge protection module is functioning correctly.
- 5 During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
- 6 Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions (FAQ)
What is the maximum discharge current (Imax) for this surge protective device?
The maximum discharge current (Imax) for this device is 40kA (8/20μs), utilizing 34S MOV technology.
How does the status indicator window work?
Under normal operating status, the indicator window displays green. If the product malfunctions or falls, the window turns red, signaling that the module needs to be replaced.
What are the operating temperature limits for this SPD?
The device is designed to operate reliably within an environmental temperature range of -40°C to +80°C.
Does this product support remote monitoring?
Yes, a remote signaling function is optional. When configured, it outputs a remote alarm signal if the module fails.
What mounting standard is required for installation?
This surge protection device is designed for easy installation on standard 35mm DIN rails.
What connection precautions should be taken during installation?
Always disconnect power before installation. Connect DC+ to the positive pole, DC- to the negative pole, and PE to the ground wire. Ensure all parallel-connected wires are secure, short, thick, and straight.