1500V DC 3-Pole Type 2 Surge Protection Device for Solar Systems - China Supplier & Factory
Model Meaning
Product Principle and Working Conditions
Meets ClassⅡ (8/20μs) SPD tests
Based on zinc oxide technology
Using 34S MOV, the maximum will be up to 8/20μs 40kA
No power frequency continuous flow
The operating environment temperature is -40°C~+80°C
Remote signaling function is optional
When product falls, the green window turns to red and remote signaling provides remote alarm function
Technical Parameter Details
| Technical Data | ||||
|---|---|---|---|---|
| POLE | 3P | |||
| SPD Type | Type 2/ClassⅡ | |||
| Technology | MOV/MOV+GDT | |||
| Protection mode(s) | DC+PE.DC | |||
| Max.continuous operating voltage (D.c.) [Ucpv] | 800V | 1000V | 1200V | 1500V |
| Nominal discharge current(8/20μs) [In] | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | |||
| Protection level [Up] | ≤3.6kV | ≤4.0kV | ≤4.5kV | ≤5.2kV |
| Response time [tA] | ≤25ns | |||
| Admissible short-circuit current [lsccr] | 25kA | |||
| Max. backup fuse | 125AgL/Gg | |||
Mechanical Data
| Mechanical Data | ||||
|---|---|---|---|---|
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DlN rail | |||
| Housing material | Thermoplastic,UL 94 V-O | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A;125V/0.2A;75V/0.5A | |||
| Certification | CE,CB,RoHS,TUV | |||
Outer Appearance and Installation Dimensions
Installation Considerations
1. Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
2. It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
3. Follow the installation diagram for connection during installation. DC+ is the positive pole, DC- is the negative pole, and PE is the ground wire. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
4. After installation, insert the module into place and verify if the surge protection module is functioning correctly.
5. During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
6. Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions (FAQ)
What is the operating temperature range for this surge protection device?
The operating environment temperature for this surge protection device is -40°C to +80°C.
How do I know when the surge protection module needs to be replaced?
During use, you should regularly inspect the status of the fault display window. If the window turns from green to red, or if the optional remote signaling terminal outputs an alarm signal, it indicates a malfunction, and the module should be replaced promptly.
What are the maximum discharge current specifications?
Based on zinc oxide technology and using a 34S MOV, the maximum discharge current (Imax) is up to 40kA (8/20μs), and the nominal discharge current (In) is 20kA.
What type of mounting configuration does this SPD use?
The device is pluggable and designed to be mounted on a standard 35mm DIN rail.
What precautions should be taken regarding the wiring during installation?
For parallel-connected installations, the connection wires must be secure, reliable, short, thick, and straight. Always ensure DC+ is connected to the positive pole, DC- to the negative pole, and PE to the ground wire.