275V AC 3-Pole Surge Protective Device Type 1+2 | China Suppliers & Factory | LKX-T1T2-AC
- 10/350, 8/20us varistor; Lightning impulse current to Iimp 10kA.
- Three-poles high discharge capacity surge arrester.
- Consist of varistors and thermal disconnection devices.
- Double terminal for parallel or series (V-shape) connection.
- Multifunctional connection for conductors and busbar.
- Windows will change to red when fault and also provide remote alarm control at the same time.
| Type | LKX-B+C 275V 10kA |
| Rated voltage (max. continuous voltage) [Uc] | 275V AC |
| Lightning impulse current (10/350) [Iimp] | 10kA |
| Nominal discharge current (8/20) [In] | 20kA |
| Max. discharge current (8/20) [Imax] | 40kA |
| Voltage protection level at In [Up] | ≤ 1.5kV |
| Response time [tA] | ≤ 25ns |
| TOV voltage | 335V/5sec |
| Max. back up fuse [L] | 200A gL/gG |
| Max. back up fuse [L-L’] | 125A gL/gG |
| Operating temperature range [Tu] | -40°C...+80°C |
| Cross-sectional area | 35mm² solid / 50mm² flexible |
| Mounting on | 35mm DIN rail |
| Enclosure material | Light grey thermoplastic, UL94-V0 |
| Dimension | 2 mods (36mm) |
| Test standards | IEC 61643-11; EN 61643-11; GB18802.11 |
| Certification | CE (LVD, EMC); ISO |
| Type of remote signalling contact | Switching contact |
| Switching capacity | AC:250V/0.5A; DC:250V/0.1A; 150V/0.2A; 750V/0.5A |
| Cross-sectional area for remote signalling contact | Max. 1.5mm² solid / flexible |
| Packing unit | 1pc(s) |
- ✔️ Three-phase surge protection
- ✔️ Main switchboard lightning protection
- ✔️ 275V AC power supply systems
- ✔️ T1+T2 combined SPD for industrial applications
- ✔️ High-energy surge protection device for commercial buildings
- ✔️ DIN rail mounted SPD for distribution boards
- ✔️ AC surge suppressor for lightning-prone areas
This device is designed for installation at LPZ 0A-1 boundaries or higher. It acts as a Class I+II (Class B+C) combined surge protective device, protecting low-voltage electrical equipment from transient overvoltages and lightning surges.
The device features local inspection windows. When a fault occurs or the module is degraded, the window changes from green to red. It also features remote alarm contacts to alert operators of system faults simultaneously.
The LKX-B+C is fully designed and certified in accordance with international standards IEC 61643-11, EN 61643-11, and GB18802.11, and holds CE (LVD, EMC) and ISO certifications.
It features double terminals for parallel or series (V-shape) connection, offering a multifunctional connection interface suitable for both standard conductors and busbars.
The Iimp (10kA) measures the direct lightning impulse current handling capability using a 10/350 μs waveform, while the In (20kA) measures the nominal discharge current handling capability using an 8/20 μs waveform for induced surges.