Main Technical Data
| Product model | LKX-A25 |
| Applicable power supply | 220/385V~50Hz |
| Maximum continuous operating voltage (Uc) | 275V/385V |
| Insulation resistance (Rins) | >100Mohm |
| Ipeak current | 25KA |
| Charge quantity | 7.5AS |
| Energy (W/R) | 56.25KJ/Q |
| In (8/20μs) | 25KA |
| Imax (8/20μs) | 100KA |
| Voltage protection level | ≤2.2KA |
| Response time | ≤100ns |
| Operating temperature | -40~+80℃ |
| Enclosure material | Flame-retardant nylon |
| Protection rating | IP20 |
| Install a fuse before the SPD | 125A |
| The cross-sectional area of the conductor after connection | 6-35mm² |
02
Normal operating conditions and installation conditions
- ✓ Ambient temperature: -40°C to +80°C.
- ✓ Altitude: Not exceeding 2000m above sea level.
- ✓ Relative humidity: Not exceeding 90% (25°C).
- ✓ Installation method: Compatible with 35mm standard DIN rail.
- ✓ Suitable grounding types: "IT", "TT", "TS", "TN-C-S", "TN-S".
- ✓ Maximum inclination angle relative to the vertical plane: 50°.
- ✓ Installation location: Free from impact vibration or oscillation.
- ✓ Environment: Free from explosive atmospheres and from gases and dust that can corrode metal or damage insulation.
03
Outer appearance and installation dimensions
Frequently Asked Questions (FAQ)
What is the maximum continuous operating voltage (Uc) of this SPD?
The maximum continuous operating voltage (Uc) for this Surge Protective Device (SPD) is 275V/385V, making it suitable for 220/385V~50Hz power supply systems.
What is the recommended installation method?
This device is designed to be compatible with a standard 35mm DIN rail for easy and secure installation inside electrical distribution boards.
What grounding systems are compatible with the LKX-A25 SPD?
The LKX-A25 is highly versatile and suitable for various grounding system configurations including "IT", "TT", "TS", "TN-C-S", and "TN-S".
What are the environmental limits for operating this device?
It operates reliably in ambient temperatures ranging from -40°C to +80°C, at altitudes not exceeding 2000m, and in relative humidity up to 90% (at 25°C).
Does this SPD require an upstream fuse?
Yes, it is recommended to install a 125A fuse upstream before the SPD to ensure proper circuit protection and system safety.