385V AC Type 2 Surge Protective Device | LKX-C40 - Reliable Protection from China Suppliers and Factory
Product principle and working conditions
- Meets Class Ⅱ (8/20 μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20μs 40ka
- No power frequency continuous flow
- Compact, yet high surge rated pluggable design, using minimum 35mm DIN rail width
- The operating environment temperature is -40℃~+80℃
- Red/Green status indication and change-over contacts standard for remote monitoring. (Remote function is Option)
Technical parameter details
| Technical Data | |||||
|---|---|---|---|---|---|
| POLE | 2P/2+0 | ||||
| Technology | MOV (Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE/N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max. continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current (8/20μs) [In] | 20kA | 20kA | |||
| Max. discharge current (8/20μs) [Imax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | - | |||
| Temporary overvoltage (TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [Isccr] | 25kA | ||||
| Max. backup fuse | 63AgL/Gg | ||||
Mechanical Data
| Mechanical Data | ||||
|---|---|---|---|---|
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DIN rail | |||
| Housing material | Thermoplastic, UL 94 V-0 | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max. Voltage/Current for remote signaling | Max 1.5mm² solid/flexible | |||
| Standards compliance | 250V/0.1A; 125V/0.2A; 75V/0.5A | |||
| Certification | CE, CB, RoHS, TUV | |||
Outer appearance and installation dimensions
Installation considerations
- Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
- It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
- Follow the installation diagram for connection during installation. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
- After installation, insert the module into place and verify if the surge protection module is functioning correctly.
- During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
- Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions (FAQ)
What is the operating temperature range for this surge protection module?
The operating environment temperature for this device ranges from -40℃ to +80℃, making it suitable for standard industrial and outdoor conditions.
How does the status indicator work on this SPD?
The module features a visual Red/Green status window. Green indicates the module is operating normally, while Red indicates a fault, meaning the surge protection module must be replaced immediately.
What installation method is required for this surge protector?
This device features a compact, pluggable design compatible with standard 35mm DIN rail mounting, ensuring quick and easy integration into electrical cabinets.
Is a backup fuse necessary during installation?
Yes, it is highly recommended to install a fuse or circuit breaker (up to 63AgL/Gg) in series at the front end of the surge protection module to ensure safe maintenance and operation.
What certifications does this surge protection device hold?
This SPD is fully compliant with international safety and quality standards and holds CE, CB, RoHS, and TUV certifications.