Leave Your Message
800V 3P T2 Surge Protection Device for DC Systems | China Suppliers & Factory - LKX-PV
Hot Products

800V 3P T2 Surge Protection Device for DC Systems | China Suppliers & Factory - LKX-PV

The **Type 2 SPD Surge Protective Device 20–40kA 800V DC 3-Pole (LKX-PV)** offers dependable Class II surge protection specially designed for **medium-to-high voltage DC and photovoltaic systems**. This device effectively mitigates transient overvoltage, switching surges, and induced lightning currents. Engineered with **high-energy MOV modules, thermal disconnection protection, and rapid response performance**, it guarantees optimal safety for **PV arrays, combiner boxes, multi-string inverters, DC distribution panels, energy-storage systems, and 800V DC off-grid or hybrid solar installations**. As a leading **China supplier** specializing in advanced surge protection technology, our products are manufactured in-house at our state-of-the-art **factory**, ensuring unmatched quality and reliability for your solar energy solutions.

    01Model Meaning
    Model Meaning
    02Product principle and working conditions
    • Meets ClassⅡ (8/20μs) SPD tests
    • Based on zinc oxide technology
    • Using 34S MOV, the maximum will be up to 8/20 μs 40kA
    • No power frequency continuous flow
    • The operating environment temperature is -40°C~+80°C
    • Remote signaling function is optional.
    • When product falls, the green window turns to red and remote signaling provides remote alarm function
    03Technical parameter details
    Technical Data
    POLE 3P
    SPD Type Type 2/ClassⅡ
    Technology MOV/MOV+GDT
    Max.continuous operating voltage 800V 1000V 1200V 1500V
    Nominal discharge current 20kA
    Max.discharge current 40kA
    04Mechanical Data
    Mounting 35mm DlN rail
    Housing material Thermoplastic,UL 94 V-O
    Protection rating IP20
    Certification CE,CB,RoHS,TUV
    05Outer appearance and installation dimensions
    Dimensions 1 Dimensions 2
    06Installation considerations
    • Confirm complete power isolation before installation.
    • The input side should incorporate a fuse or circuit breaker.
    • Ensure proper polarity: DC+, DC-, and PE grounding.
    • Conduct functional verification immediately after installation.
    • Perform periodic maintenance and check diagnostic indicators.

    Frequently Asked Questions (FAQ)

    Q: What is the operating temperature range?
    A: The operating environment temperature is -40°C to +80°C.
    Q: Does it support remote signaling?
    A: Yes, the remote signaling function is optional.
    Q: What is the protection rating?
    A: The device has an IP20 protection rating.
    Q: What certifications do these SPDs have?
    A: They are certified with CE, CB, RoHS, and TUV.
    Q: How to identify a device failure?
    A: If the green window turns to red, it signifies device failure.