800V 3P T2 Surge Protection Device - Reliable China Factory Suppliers for DC & PV Systems
Model Meaning
Product principle and working conditions
- Meets ClassⅡ (8/20μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20 μs 40kA
- No power frequency continuous flow
- The operating environment temperature is -40°C~+80°C
- Remote signaling function is optional.
- When product falls, the green window turns to red and remote signaling provides remote alarm function
Technical parameter details
| Technical Data | ||||
| POLE | 3P | |||
| SPD Type | Type 2/ClassⅡ | |||
| Technology | MOV/MOV+GDT | |||
| Protection mode(s) | DC+PE.DC | |||
| Max.continuous operating voltage (D.c.) [Ucpv] | 800V | 1000V | 1200V | 1500V |
| Nominal discharge current(8/20μs) [In] | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | |||
| Protection level [Up] | ≤3.6kV | ≤4.0kV | ≤4.5kV | ≤5.2kV |
| Response time [tA] | ≤25ns | |||
| Admissible short-circuit current [lsccr] | 25kA | |||
| Max. backup fuse | 125AgL/Gg | |||
Mechanical Data
| Mechanical Data | ||||
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DlN rail | |||
| Housing material | Thermoplastic,UL 94 V-O | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A;125V/0.2A;75V/0.5A | |||
| Certification | CE,CB,RoHS,TUV | |||
Outer appearance and installation dimensions
Installation considerations
- 1. Prior to installation, confirm complete power isolation. Any operation under live conditions is expressly forbidden.
- 2. The surge protector's input side should incorporate an in-line fuse or circuit breaker as protective measure.
- 3. Adhere strictly to the provided wiring schematic: DC+ denotes positive terminal, DC- indicates negative terminal, and PE represents grounding conductor. Ensure proper polarity during installation. Upon completion, activate the protective device (circuit breaker/fuse) and validate normal operational parameters.
- 4. Following installation, properly position the unit and conduct functional verification of the surge protective device.
- 5. Implement periodic maintenance checks on the surge protector, including monitoring of the diagnostic indicator. A red warning display or alarm contact activation signifies device failure requiring immediate attention through repair or replacement.
- 6. When installing multiple surge protectors in parallel configuration, maintain true parallel wiring with properly secured connections using appropriately sized conductors of minimal length and direct routing.
Frequently Asked Questions (FAQ)
What is the maximum discharge current (Imax) for this Surge Protective Device (SPD)?
The maximum discharge current (Imax) with an 8/20μs waveform is 40kA, while the nominal discharge current (In) is 20kA.
What do the green and red colors on the visual indicator window mean?
A green window indicates that the SPD is operating normally. If the window turns red, it indicates device failure, and the remote signaling function (if installed) will trigger an alarm, signaling that the unit needs immediate replacement.
What technology is used in this product for surge protection?
This SPD is based on advanced zinc oxide technology utilizing a 34S MOV (Metal Oxide Varistor) or a combination of MOV and GDT (Gas Discharge Tube) to ensure high-reliability protection without power frequency continuous flow.
What are the environmental and operating temperature limits?
The device is designed to operate reliably in harsh environments, with an operating temperature range of -40°C to +80°C.
How should the device be wired and installed?
Installation must be done under complete power isolation. You must follow the wiring schematic: connect DC+ to the positive terminal, DC- to the negative terminal, and PE to the grounding conductor. The device supports standard 35mm DIN rail mounting.