Best Surge Protection Device for Solar Panels - LKX-T1T2-DC - China Suppliers Factory 20-40kA 1200V DC
Technical Specifications
| Specification | LKX-1200-6.25 | |
|---|---|---|
| SPD classification according to EN61643-31 / IEC61643-31 | Type 1 + Type 2 / Class I + Class II | |
| Max. continuous operating d.c. voltage | Ucpv | 1200V |
| Lightning impulse current (10/350μs) | Iimp | 6.25kA |
| Nominal discharge current (8/20μs) | In | 20kA |
| Max. discharge current (8/20μs) | Imax | 40kA |
| Residucal current | Ipe(DC) | <0.02mA |
| Specific energy | W/R | 9.76kJ/Ω |
| Voltage protection level [(DC+/DC-)→PE] | Up | ≤4.5kV |
| Short-circuit current rating | Iscpv | 10kA |
| Response time | tA | ≤25ns |
| Operating temperature range | Tu | -40ºC - 80ºC |
| Operating state / fault indication | green / red | |
| Cross-section area (Min.) | 4mm² | |
| Cross-section area (Max.) | 35mm² | |
| For mounting on | 35mm Din rail | |
| Enclosure material | Thermoplastic UL94-V0 | |
| Degree of protection | IP20 | |
| Order code | LKX12003625 | |
| Order code (with remote signal) | LKX12003625-1 | |
Features
- Thermal disconnect device for each individual connector
- Normal discharge current (8/20us) In: 20kA
- Mechanical status indication for the individual surge protective device module
- High energy varistors
- With or without floating remote indication contact
Application
- LKX Surge protective device, protect against lightning surge voltages in solar system (photovoltaic power supply system).
- Used for surge protection of electrical components in any other DC circuit.
- These units must be installed in parallel on the DC networks to be protected and provide common and different modes protection.
- It is suitable for surge protection of DC power supply line equipment of solar power generation system.
Installation and Maintenance
Installed in parallel at the interface of LPZ1 zone and subsequent zones: power controller, power converter, etc.
When the surge arrester is installed under the required conditions, it does not require long-term maintenance, but only routine maintenance. If the color of the visible alarm window changes to red (fault) during use, it indicates that the surge protector is damaged and needs to be repaired or replaced.
Frequently Asked Questions (FAQ)
What is the primary application of the LKX-1200-6.25 surge protective device?
It is designed to protect against lightning surge voltages in solar systems (photovoltaic power supply systems) and other DC circuits, protecting electrical components from overvoltage damage.
How do I know if the surge protective device is damaged?
The device features a mechanical status indicator. If the color of the visible alarm window changes from green to red, it indicates a fault, meaning the surge protector is damaged and must be replaced.
Where should the LKX surge protective device be installed?
It must be installed in parallel on the DC networks to be protected, specifically at the interface of the LPZ1 zone and subsequent zones (such as power controllers and power converters).
Does this surge protective device require regular maintenance?
Under proper installation conditions, the device does not require long-term maintenance. Only routine visual inspections of the status indicator window are needed.
What are the main technical parameters of the LKX-1200-6.25?
Key parameters include a maximum continuous operating DC voltage (Ucpv) of 1200V, a lightning impulse current (Iimp) of 6.25kA, a nominal discharge current (In) of 20kA, and a response time of ≤25ns.