| Specification | LKX-1200-6.25 | |
|---|---|---|
| SPD classification according to EN61643-31 / IEC61643-31 | Type 1 + Type 2 / Class I + Class II | |
| Max. continuous operating d.c. voltage | Ucpv | 1200V |
| Lightning impulse current (10/350μs) | Iimp | 6.25kA |
| Nominal discharge current (8/20μs) | In | 20kA |
| Max. discharge current (8/20μs) | Imax | 40kA |
| Residucal current | Ipe(DC) | <0.02mA |
| Specific energy | W/R | 9.76kJ/Ω |
| Voltage protection level [(DC+/DC-)→PE] | Up | ≤4.5kV |
| Short-circuit current rating | Iscpv | 10kA |
| Response time | tA | ≤25ns |
| Operating temperature range | Tu | -40℃-80℃ |
| Operating state / fault indication | green / red | |
| Cross-section area (Min.) | 4mm² | |
| Cross-section area (Max.) | 35mm² | |
| For mounting on | 35mm Din rail | |
| Enclosure material | Thermoplastic UL94-V0 | |
| Degree of protection | IP20 | |
| Order code | LKX12003625 | |
| Order code (with remote signal) | LKX12003625-1 | |
Features
- Thermal disconnect device for each individual connector
- Normal discharge current (8/20us) In: 20kA
- Mechanical status indication for the individual surge protective device module
- High energy varistors
- With or without floating remote indication contact
Application
- LKX Surge protective device protects against lightning surge voltages in solar systems (photovoltaic power supply system).
- Used for surge protection of electrical components in any other DC circuit.
- These units must be installed in parallel on the DC networks to be protected and provide common and different modes protection.
- It is suitable for surge protection of DC power supply line equipment of solar power generation systems.
Installation and Maintenance
- Installed in parallel at the interface of LPZ1 zone and subsequent zones: power controller, power converter, etc.
When the surge arrester is installed under the required conditions, it does not require long-term maintenance, but only routine maintenance. If the color of the visible alarm window changes to red (fault) during use, it indicates that the surge protector is damaged and needs to be repaired or replaced.
Frequently Asked Questions
The LKX Surge Protective Device is primarily designed to protect against lightning surge voltages in solar systems (photovoltaic power supply systems) and other DC power supply line equipment.
The device features a mechanical status indication window. Under normal operation, it displays green. If the window changes to red, it indicates a fault, meaning the device is damaged and must be repaired or replaced.
It should be installed in parallel on the DC networks to be protected, specifically at the interface of the LPZ1 zone and subsequent zones, such as near the power controller or power converter.
This surge protective device is designed for easy installation and is mounted directly on standard 35mm Din rails.
No. When installed under the required operating conditions, the device does not require long-term maintenance, only standard routine visual checks of the status indicator.