Best Surge Protection Device for Solar Panels - LKX-T1T2-DC from China Suppliers and Factory, 20-40kA 1200V DC
Specification
| Parameter | LKX-1200-6.25 | |
|---|---|---|
| SPD classification according to EN61643-31 / IEC61643-31 | Type 1 + Type 2 / Class I + Class II | |
| Max. continuous operating d.c. voltage | Ucpv | 1200V |
| Lightning impulse current (10/350μs) | Iimp | 6.25kA |
| Nominal discharge current (8/20μs) | In | 20kA |
| Max. discharge current (8/20μs) | Imax | 40kA |
| Residual current | Ipe(DC) | <0.02mA |
| Specific energy | W/R | 9.76kJ/Ω |
| Voltage protection level [(DC+/DC-)→PE] | Up | ≤4.5kV |
| Short-circuit current rating | Iscpv | 10kA |
| Response time | tA | ≤25ns |
| Operating temperature range | Tu | -40℃ - 80℃ |
| Operating state / fault indication | green / red | |
| Cross-section area (Min.) | 4mm² | |
| Cross-section area (Max.) | 35mm² | |
| For mounting on | 35mm Din rail | |
| Enclosure material | Thermoplastic UL94-V0 | |
| Degree of protection | IP20 | |
| Order code | LKX12003625 | |
| Order code (with remote signal) | LKX12003625-1 | |
Key Features
-
Thermal disconnect device for each individual connector.
-
Normal discharge current (8/20us) In: 20kA.
-
Mechanical status indication for the individual surge protective device module.
-
High energy varistors integrated for reliable protection.
-
Available with or without floating remote indication contact.
Applications
-
Solar Photovoltaic Systems: LKX Surge protective device protects against lightning surge voltages in solar systems (photovoltaic power supply systems).
-
DC Power Supply Lines: Suitable for surge protection of DC power supply line equipment of solar power generation systems.
-
DC Circuit Components: Used for surge protection of electrical components in any other DC circuit.
-
Parallel Network Protection: These units must be installed in parallel on the DC networks to be protected and provide common and different modes protection.
Installation and Maintenance
Installed in parallel at the interface of LPZ1 zone and subsequent zones: power controller, power converter, etc.
When the surge arrester is installed under the required conditions, it does not require long-term maintenance, but only routine maintenance. If the color of the visible alarm window changes to red (fault) during use, it indicates that the surge protector is damaged and needs to be repaired or replaced.
Frequently Asked Questions (FAQ)
What is the application of the LKX Surge Protective Device?
The LKX Surge Protective Device is designed to protect against lightning surge voltages in solar systems (photovoltaic power supply systems) and other DC power supply circuits.
How do I know if the surge protector is damaged?
The device features a mechanical status indication window. If the visible alarm window changes from green (normal operating state) to red (fault), it indicates that the surge protector is damaged and needs to be repaired or replaced.
Where should the LKX surge protective device be installed?
It should be installed in parallel at the interface of the LPZ1 zone and subsequent zones, such as next to power controllers or power converters.
Does the device require regular maintenance?
No, when installed under the required conditions, it does not require long-term maintenance. Only routine visual inspections of the status indicator are necessary.
What is the DIN rail mounting size and standard classification?
The device is designed for mounting on a 35mm DIN rail. It conforms to the Type 1 + Type 2 / Class I + Class II SPD classifications according to EN61643-31 and IEC61643-31 standards.