How to install surge protection device 320V 2P Type 2| LKX-C40
01
Product principle and working conditions
1.Meets Class ll (8/20 μs ) SPD tests.
2. Based on Zinc Oxide Technology
3. Using 34S MOV, the maximum is up to 8/20μs 40kA.
4. No power frequency, continuous flow
5. Compact, yet high surge rated pluggable design, with a minimum 35mm DIN rail width.
6. The operational temperature range is -40℃ to +80℃.
7.For remote monitoring, red/green status indication and changeover contacts are standard.(Remote function is optional).
2. Based on Zinc Oxide Technology
3. Using 34S MOV, the maximum is up to 8/20μs 40kA.
4. No power frequency, continuous flow
5. Compact, yet high surge rated pluggable design, with a minimum 35mm DIN rail width.
6. The operational temperature range is -40℃ to +80℃.
7.For remote monitoring, red/green status indication and changeover contacts are standard.(Remote function is optional).
02
Technical parameter details
| Technical Data | |||||
| POLE | 2P/2+0 | ||||
| Technology | MOV(Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE/N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max.continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current(8/20μs) [In] | 20kA | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Responsee time [tA] | ≤25ns | ||||
| Temporary overvoltage(TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [lsccr] | 25kA | ||||
| Max, backup fuse | 63AgL/Gg | ||||
03
Mechanical Data
| Mechanical Data | ||||
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DlN rail | |||
| Housing material | Thermoplastic,UL 94 V-O | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A;125V/0.2A;75V/0.5A | |||
| Certification | CE, CB, RoHS,TUV | |||
04

Outer appearance and installation dimensions


05
As a company that focuses on technological innovation and product quality, we are committed to providing our customers with safe, reliable and superior performance products. We firmly believe that this product will bring you convenience and enjoyment, and we will make unremitting efforts and continuous innovation to meet your needs. Please do not hesitate to contact us immediately and we look forward to providing you with more help and support.
Installation considerations
1.Be sure to turn off the power before beginning the installation. Operating when energized is strictly banned.
2.A fuse or circuit breaker should be installed in series at the front of the surge protection module.
3.Connect according to the installation diagram throughout the installation process. Avoid making improper connections. After installation, close the circuit breaker (or fuse) switch and ensure that the operation is OK.
2.A fuse or circuit breaker should be installed in series at the front of the surge protection module.
3.Connect according to the installation diagram throughout the installation process. Avoid making improper connections. After installation, close the circuit breaker (or fuse) switch and ensure that the operation is OK.
4.After installation, insert the module and check that the surge protection module is working properly.
5.During operation, inspect the surge protection module on a regular basis and monitor the state of the fault display window. If the fault display window turns red or the remote signaling terminal emits an alarm signal, it indicates that the surge protection module is malfunctioning and should be repaired or replaced immediately.
6.Install power surge protection units in parallel. The connection wires must be sturdy, dependable, short, thick, and straight.
5.During operation, inspect the surge protection module on a regular basis and monitor the state of the fault display window. If the fault display window turns red or the remote signaling terminal emits an alarm signal, it indicates that the surge protection module is malfunctioning and should be repaired or replaced immediately.
6.Install power surge protection units in parallel. The connection wires must be sturdy, dependable, short, thick, and straight.
As a company that focuses on technological innovation and product quality, we are committed to providing our customers with safe, reliable and superior performance products. We firmly believe that this product will bring you convenience and enjoyment, and we will make unremitting efforts and continuous innovation to meet your needs. Please do not hesitate to contact us immediately and we look forward to providing you with more help and support.