China Factory Suppliers Transient Voltage Surge Suppressor 275V 2P Type 2 | Class II SPD 20-40kA Protection
01
Product Principle and Working Conditions
- Meets Class II (8/20μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20μs 40kA
- No power frequency continuous flow
- Compact, yet high surge rated pluggable design, using minimum 35mm DIN rail width
- The operating environment temperature is -40℃~+80℃
- Red/Green status indication and change-over contacts standard for remote monitoring (Remote function is option)
02
Technical Parameter Details
| Technical Data | |||||
|---|---|---|---|---|---|
| POLE | 2P/2+0 | ||||
| Technology | MOV (Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE/N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max. continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current (8/20μs) [In] | 20kA | 20kA | |||
| Max. discharge current (8/20μs) [Imax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | - | |||
| Temporary overvoltage (TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [Isccr] | 25kA | ||||
| Max. backup fuse | 63AgL/Gg | ||||
03
Mechanical Data
| Mechanical Specification | ||||
|---|---|---|---|---|
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DIN rail | |||
| Housing material | Thermoplastic, UL 94 V-0 | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max. Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A; 125V/0.2A; 75V/0.5A | |||
| Certification | CE, CB, RoHS, TUV | |||
04
Outer Appearance and Installation Dimensions
05
Installation Considerations
1
Make sure the electricity is turned off before installation. It is completely forbidden to operate when electrified.
2
It is advised to connect a circuit breaker or fuse in series with the surge protection module's front end.
3
During installation, adhere to the installation schematic for connection. Steer clear of bad connections. Close the circuit breaker (or fuse) switch after installation, then make sure everything is operating normally.
4
After installation, make sure the surge protection module is operating properly by putting it in place.
5
Check the condition of the fault display window and conduct routine inspections of the surge protection module while in use. The surge protection module needs to be changed or repaired right away if the fault display window turns red or if the remote signaling terminal emits an alert signal.
6
It is recommended to install parallel-connected power surge protection devices. The connection wires need to be straight, short, thick, dependable, and secure.
Frequently Asked Questions (FAQ)
What technology is this surge protective device (SPD) based on?
This surge protective device is based on advanced zinc oxide technology and utilizes a 34S MOV (Metal Oxide Varistor) to deliver high reliability and performance.
What is the operating temperature range for this SPD?
The operating environment temperature range for this surge protective device is from -40℃ up to +80℃, making it suitable for standard and harsh environmental conditions.
How does the status indicator work on this device?
The device features a Red/Green visual status window. Green indicates the device is operating normally, while Red indicates a fault, meaning the module must be replaced immediately. Optional remote signaling contacts are also available for remote monitoring.
What is the maximum discharge current (Imax) for this SPD?
The maximum discharge current (Imax) at 8/20μs is 40kA, with a nominal discharge current (In) of 20kA.
What are the mounting and installation requirements?
The device features a pluggable design compatible with standard 35mm DIN rails. Ensure the electricity is completely turned off during installation, use short and thick connection wires, and install a circuit breaker or fuse in series at the front end.