China Factory Suppliers: Type 2 600V 2-Pole Surge Protection Device for Solar PV Systems (LKX-PV)
Hot Products

China Factory Suppliers: Type 2 600V 2-Pole Surge Protection Device for Solar PV Systems (LKX-PV)

The **Type 2 SPD Surge Protective Device 20–40kA 600V DC 2-Pole (LKX-PV)** is a top-tier solution designed for **photovoltaic and DC power systems**. This device offers essential Class II protection against transient overvoltages, switching surges, and lightning-induced currents. Utilizing advanced **high-energy MOV + thermal disconnector technology**, it guarantees quick response times, stable DC performance, and durable protection for a range of applications, including **solar PV arrays, combiner boxes, string inverters, DC distribution panels, energy-storage systems, and off-grid power installations**. As a leading **supplier and factory** in **China**, we are committed to providing reliable surge protection devices that ensure the longevity and efficiency of your energy systems.

    01

    Model Meaning

    Model Meaning Diagram
    02

    Product Principle and Working Conditions

    • Meets Class &IIota; (8/20μs) SPD tests
    • Based on zinc oxide technology
    • Using 34S MOV, the maximum will be up to 8/20μs 40kA
    • No power frequency continuous flow
    • The operating environment temperature is -40°C~+80°C
    • Remote signaling function is optional
    • When product falls, the green window turns to red and remote signaling provides remote alarm function
    03

    Technical Parameter Details

    POLE 2P / 2+0
    Technology MOV (Metal Oxide Varistors) GDT
    Protection mode(s) L-PE / N-PE NPE
    Nominal voltage (A.C.) [Un] 220V 300V 380V 400V 225V
    Max.continuous operating voltage (D.C.) [Ucpv] 275V 320V 385V 420V 225V
    Nominal discharge current (8/20μs) [In] 20kA 20kA
    Max.discharge current (8/20μs) [Imax] 40kA 40kA
    Protection level [Up] ≤1.5kV ≤1.6kV ≤1.8kV ≤2.0kV ≤1.5kV
    Response time [tA] ≤25ns -
    Temporary overvoltage (TOV) withstand - 5 sec [Ut] 335V 440V 440V 620V 335V
    Admissible short-circuit current [Isccr] 25kA
    Max. backup fuse 63AgL/Gg
    04

    Mechanical Data

    Current AC system
    SPD configuration Single / Three phase
    Pluggable Available
    Mounting 35mm DIN rail
    Housing material Thermoplastic, UL 94 V-0
    Operating temperature -40℃...+80℃
    Protection rating IP20
    Remote Signaling Green / Red
    Wiring for remote signaling Optional
    Max. Voltage/Current for remote signaling Max 1.5mm solid / flexible
    Standards compliance 250V/0.1A; 125V/0.2A; 75V/0.5A
    Certification CE, CB, RoHS, TUV
    05

    Outer Appearance and Installation Dimensions

    Outer Appearance Dimension 1
    Installation Dimension Diagram 2
    06

    Installation Considerations

    1. Prior to installation, make sure the power supply is turned off. Working on live equipment is strictly forbidden.
    2. A fuse or circuit breaker should be connected in series upstream of the surge protector for added safety.
    3. Refer to the wiring diagram for proper installation. Connect DC+ to the positive terminal, DC- to the negative terminal, and PE to the grounding wire. Ensure correct polarity to prevent wiring errors. Once installed, turn on the circuit breaker (or fuse) and verify normal operation.
    4. Once installed, securely mount the module and confirm that the surge protector is operating as intended.
    5. Periodically check the surge protector and monitor the fault indicator. A red fault indicator or an alarm signal from the remote terminal means the surge protector has failed and must be repaired or replaced immediately.
    6. For parallel-connected surge protectors, ensure proper parallel wiring. Use short, thick, straight, and securely fastened cables for optimal performance.
    FAQ

    Frequently Asked Questions

    Q: What is the response time of this surge protector?
    The response time (tA) of the MOV technology is ≤25ns, providing rapid protection against transient voltage spikes.
    Q: How do I know if the surge protective device needs replacement?
    The unit features a visual status window. Normal operating mode is indicated by green; when it fails, the window turns red, and the remote signaling module will trigger an alarm.
    Q: What mounting type is required for installation?
    It is designed for standard 35mm DIN rail mounting, making it easy to integrate into conventional distribution boxes and panels.
    Q: What certifications does this product comply with?
    This SPD complies with international safety standards and is certified with CE, CB, RoHS, and TUV.
    Q: What is the recommended backup fuse for this surge protection device?
    The maximum recommended backup fuse upstream is 63AgL/Gg to ensure safe and coordinated operation.