China Factory Suppliers Type 2 SPD Surge Protective Device 1000V DC 3P for Photovoltaic Systems
01Model Meaning
02Product principle and working conditions
- 1Meets ClassⅡ (8/20μs) SPD tests
- 2Based on zinc oxide technology
- 3Using 34S MOV, the maximum will be up to 8/20 μ s 40kA
- 4No power frequency continuous flow
- 5The operating environment temperature is -40°C~+80°C
- 6Remote signaling function is optional.
- 7When product falls, the green window turns to red and remote signaling provides remote alarm function
03Technical parameter details
| Technical Data | ||||
|---|---|---|---|---|
| POLE | 3P | |||
| SPD Type | Type 2/ClassⅡ | |||
| Technology | MOV/MOV+GDT | |||
| Protection mode(s) | DC+PE.DC | |||
| Max.continuous operating voltage (D.c.) [Ucpv] | 800V | 1000V | 1200V | 1500V |
| Nominal discharge current(8/20μs) [In] | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | |||
| Protection level [Up] | ≤3.6kV | ≤4.0kV | ≤4.5kV | ≤5.2kV |
| Response time [tA] | ≤25ns | |||
| Admissible short-circuit current [lsccr] | 25kA | |||
| Max, backup fuse | 125AgL/Gg | |||
04Mechanical Data
| Mechanical Data | ||||
|---|---|---|---|---|
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DlN rail | |||
| Housing material | Thermoplastic,UL 94 V-O | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A;125V/0.2A;75V/0.5A | |||
| Certification | CE,CB,RoHS,TUV | |||
05Outer appearance and installation dimensions
06Installation considerations
- 1Verify complete power de-energization before commencing installation. Any work on active electrical systems is categorically prohibited.
- 2For optimal protection, incorporate series-connected overcurrent protection (fuse or breaker) preceding the surge suppression device.
-
3Installation wiring must strictly comply with the provided schematic:
- DC+ = Positive terminal
- DC- = Negative terminal
- PE = Protective earth ground
- 4Finalize installation by securing the module in its designated location and performing functional validation of the surge protection system.
-
5Implement scheduled maintenance inspections including:
- Visual examination of the diagnostic indicator
- Verification of alarm contact status
- Red fault indicator illumination
- Alarm signal activation
-
6Parallel surge protection configurations require:
- True parallel circuit implementation
- Properly torqued connections
- Minimum-length conductors
- Adequate wire gauge (AWG)
- Direct routing without unnecessary bends
Frequently Asked Questions (FAQ)
1. What is the maximum discharge current (Imax) for this surge protective device?
The maximum discharge current (Imax) for this device is 40kA (8/20μs) based on zinc oxide technology and the use of 34S MOV.
2. How does the status indicator window work?
The device features a green/red visual indicator. Under normal conditions, the window is green. If the surge protector fails, the window turns red, indicating that immediate replacement is required.
3. What mounting standard is required for installation?
This product is designed for standard 35mm DIN rail mounting, making it easy to integrate into standard electrical distribution panels.
4. What is the operational temperature range of this SPD?
The device is designed to operate reliably in extreme environments, with an operating environment temperature range of -40°C to +80°C.
5. Does this device support remote monitoring and alarm systems?
Yes, the remote signaling function is optional. When configured, it provides remote alarm capability that triggers when the product falls or fails (switching the indicator from green to red).
6. What wiring schematic must be followed during installation?
Wiring must strictly connect DC+ to the positive terminal, DC- to the negative terminal, and PE to the protective earth ground. Always ensure the system is completely de-energized before beginning installation.