China Factory Suppliers Type 2 SPD Surge Protective Device 275V 2-Pole LKX-C40 for Reliable Surge Protection
Product Principle and Working Conditions
- Meets Class II (8/20μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20μs 40kA
- No power frequency continuous flow
- Compact, yet high surge rated pluggable design, using minimum 35mm DIN rail width
- The operating environment temperature is -40℃ ~ +80℃
- Red/Green status indication and change-over contacts standard for remote monitoring. (Remote function is option)
Technical Parameter Details
| Technical Data | |||||
| POLE | 2P/2+0 | ||||
| Technology | MOV (Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE/N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max. continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current (8/20μs) [In] | 20kA | 20kA | |||
| Max. discharge current (8/20μs) [lmax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | ||||
| Temporary overvoltage (TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [lsccr] | 25kA | ||||
| Max. backup fuse | 63AgL/Gg | ||||
Mechanical Data
| Mechanical Data | ||||
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DIN rail | |||
| Housing material | Thermoplastic, UL 94 V-0 | |||
| Operating temperature | -40℃ ... +80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max. Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A; 125V/0.2A; 75V/0.5A | |||
| Certification | CE, CB, RoHS, TUV | |||
Outer Appearance and Installation Dimensions
Installation Considerations
- Make sure the electricity is turned off before installation. It is completely forbidden to operate when electrified.
- It is advised to connect a circuit breaker or fuse in series with the surge protection module's front end.
- During installation, adhere to the installation schematic for connection. Steer clear of bad connections. Close the circuit breaker (or fuse) switch after installation, then make sure everything is operating normally.
- After installation, make sure the surge protection module is operating properly by putting it in place.
- Check the condition of the fault display window and conduct routine inspections of the surge protection module while in use. The surge protection module needs to be changed or repaired right away if the fault display window turns red or if the remote signaling terminal emits an alert signal.
- It is recommended to install parallel-connected power surge protection devices. The connection wires need to be straight, short, thick, dependable, and secure.
Frequently Asked Questions (FAQ)
What is the maximum discharge current of this Class II SPD?
The maximum discharge current (Imax) for this Class II surge protective device is up to 40kA (8/20μs), utilizing advanced 34S MOV technology.
What are the operating temperature limits for this device?
This surge protective device is designed to operate reliably in harsh environmental conditions with a temperature range of -40℃ to +80℃.
How do I know when the surge protection module needs to be replaced?
The device features a clear Red/Green visual status indicator. Under normal conditions, it displays green. If the indicator window turns red or the optional remote signaling terminal triggers an alert, the module must be replaced immediately.
Does this SPD support remote monitoring?
Yes, change-over contacts for remote monitoring and signaling are standard, though the remote wiring function itself is optional depending on your system configuration.
What mounting standard does this surge protector use?
The device features a compact, pluggable design compatible with standard 35mm DIN rail mounting, requiring minimal installation width.
What safety precautions should be followed during installation?
Always ensure the power supply is completely shut off before starting the installation. It is highly recommended to connect a circuit breaker or fuse in series at the front end, and keep the connection wires as straight, short, and thick as possible.