China LKX-C40 Type 2 SPD Surge Protective Device 20-40kA 385V AC from Reliable Suppliers and Factory
01
Product principle and working conditions
- Meets Class Ⅱ (8/20 μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20μs 40ka
- No power frequency continuous flow
- Compact, yet high surge rated pluggable design, using minimum 35mm DIN rail width
- The operating environment temperature is -40℃~+80℃
- Red/Green status indication and change-over contacts standard for remote monitoring. (Remote function is Option)
02
Technical parameter details
| Technical Data | |||||
| POLE | 2P/2+0 | ||||
| Technology | MOV(Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE/N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max.continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current(8/20μs) [In] | 20kA | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | ||||
| Temporary overvoltage(TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [lsccr] | 25kA | ||||
| Max, backup fuse | 63AgL/Gg | ||||
03
Mechanical Data
| Mechanical Data | ||||
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DlN rail | |||
| Housing material | Thermoplastic,UL 94 V-O | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A;125V/0.2A;75V/0.5A | |||
| Certification | CE,CB,RoHS,TUV | |||
04
Outer appearance and installation dimensions
05
Installation considerations
- 1. Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
- 2. It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
- 3. Follow the installation diagram for connection during installation. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
- 4. After installation, insert the module into place and verify if the surge protection module is functioning correctly.
- 5. During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
- 6. Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions (FAQ)
Q1: What surge protection standards does this module meet?
A1: This surge protective device (SPD) meets the Class II (8/20 μs) test standards, utilizing advanced zinc oxide technology to deliver reliable surge protection.
Q2: What is the maximum discharge current capacity?
A2: Designed with a 34S MOV, the module supports a maximum discharge current (Imax) of up to 40kA (8/20μs) with a nominal discharge current (In) of 20kA.
Q3: How do I read the status indication window?
A3: The module features a visual Red/Green status indicator. Green indicates the device is operating normally, while Red indicates a malfunction, signaling that the module needs immediate replacement.
Q4: What are the installation and mounting requirements?
A4: The device features a compact, pluggable design compatible with standard 35mm DIN rails. It is suitable for both single and three-phase AC systems.
Q5: What safety precautions should be taken during installation?
A5: Ensure the power supply is completely disconnected before installation. The module must be connected in parallel using short, thick, and straight wires, and it is highly recommended to install a backup fuse or circuit breaker at the front end.