0102030405
China LKX-PV Series Surge Protector (SPD) for Solar and Wind Power - Reliable Suppliers & Factory Solutions
01
Model Meaning
02
Characteristics of the Product
- Plug-in design Surge Protective Device (SPDs)
- The visual window indicates the working status of the SPD, green(normal), red(replace)
- Dual protection of hot melt overcurrent
- Configure telecontrol interface to achieve remote control
03
Technical parameter details
| Product name | 48V DC SPD | 500V DC SPD | 600V DC SPD | 800V DC SPD | 1000V DC SPD | 1500V DC SPD |
| Product model | LKX-PV-48V | LKX-PV-500V | LKX-PV-600V | LKX-PV-800V | LKX-PV-1000V | LKX-PV-1500V |
| In (kA) | 20 | 20 | 20 | 20 | 20 | 20 |
| Imax (kA) | 40 | 40 | 40 | 40 | 40 | 40 |
| Up (kV) | 1.0 | 2.5 | 3.2 | 3.6 | 4.0 | 5.2 |
| Response time (μs) | 25 | 25 | 25 | 25 | 25 | 25 |
| Uc | 48V | 500V | 600V | 800V | 1000V | 1500V |
| Operating temperature | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ |
04
Outer appearance and installation dimensions
05
Installation considerations
- Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
- It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
- Follow the installation diagram for connection during installation. DC+ is the positive pole, DC- is the negative pole, and PE is the ground wire. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
- After installation, insert the module into place and verify if the surge protection module is functioning correctly.
- During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
- Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions
What do the green and red colors in the visual window of the SPD mean?
The visual window indicates the real-time working status of the Surge Protective Device (SPD). Green indicates that the module is working normally, while red indicates that the module has faulted and needs to be replaced.
What voltage options are available for the LKX-PV DC SPD series?
The LKX-PV series offers multiple models to suit different DC system requirements, including 48V, 500V, 600V, 800V, 1000V, and 1500V DC options.
What are the discharge current (In/Imax) ratings for these SPDs?
Across all model variations, the nominal discharge current (In) is rated at 20 kA, and the maximum discharge current (Imax) is rated at 40 kA.
What is the response time and operating temperature range for the device?
The response time of these surge protective devices is extremely fast at ≤25 microseconds, and they are designed to operate reliably in temperatures ranging from -40°C to +85°C.
How should the wiring be connected during installation?
Connections must follow the installation diagram strictly: connect DC+ to the positive pole, DC- to the negative pole, and PE to the ground wire. Ensure that the power is disconnected before starting the installation.
Why is it recommended to use a series fuse or circuit breaker with the SPD?
Installing a fuse or circuit breaker in series at the front end provides an additional layer of protection, preventing potential hazards in the event of overcurrent or short-circuits during surge events.