China LKX-PV Series Surge Protector (SPD) - Top Suppliers & Factory for Solar and Wind Energy Systems
01
Model Meaning
02
Characteristics of the Product
Plug-in design Surge Protective Device (SPDs)
The visual window indicates the working status of the SPD, green(normal), red(replace)
Dual protection of hot melt overcurrent
Configure telecontrol interface to achieve remote control
03
Technical Parameter Details
| Product name | 48V DC SPD | 500V DC SPD | 600V DC SPD | 800V DC SPD | 1000V DC SPD | 1500V DC SPD |
|---|---|---|---|---|---|---|
| Product model | LKX-PV-48V | LKX-PV-500V | LKX-PV-600V | LKX-PV-800V | LKX-PV-1000V | LKX-PV-1500V |
| In (kA) | 20 | 20 | 20 | 20 | 20 | 20 |
| Imax (kA) | 40 | 40 | 40 | 40 | 40 | 40 |
| Up (kV) | 1.0 | 2.5 | 3.2 | 3.6 | 4.0 | 5.2 |
| Response time (μs) | 25 | 25 | 25 | 25 | 25 | 25 |
| Uc | 48V | 500V | 600V | 800V | 1000V | 1500V |
| Operating temperature | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ |
04
Outer Appearance and Installation Dimensions
05
Installation Considerations
1. Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
2. It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
3. Follow the installation diagram for connection during installation. DC+ is the positive pole, DC- is the negative pole, and PE is the ground wire. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
4. After installation, insert the module into place and verify if the surge protection module is functioning correctly.
5. During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
6. Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions
Q
How do I know if the Surge Protective Device (SPD) is working or needs replacement?
The SPD features a visual inspection window. A green window indicates the device is working normally, while a red window indicates it has run its course and needs to be replaced immediately.
Q
What are the available voltage specifications for this product model?
This DC SPD series is designed to cover a wide range of voltages, including 48V, 500V, 600V, 800V, 1000V, and 1500V DC options to suit different system configurations.
Q
What safety measures must be taken before starting the installation?
Before starting the installation process, you must completely disconnect the power source. Working or installing while the system is energized is strictly prohibited to prevent electrical hazards.
Q
How should the terminals be wired during the installation process?
Refer directly to the installation diagram: connect the positive pole to DC+, the negative pole to DC-, and the ground line to PE. It is crucial to prevent reverse or incorrect connections.
Q
What is the purpose of the telecontrol interface on this SPD?
The telecontrol interface is configured to enable remote control and status signaling, allowing operators to monitor the health and performance of the surge protective device from a distance.