China LKX-PV Series Surge Protectors (SPD) - Reliable Suppliers and Factory for Solar & Wind Energy Systems
01 Model Meaning
02 Characteristics of the Product
- 1. Plug-in design Surge Protective Device (SPDs)
- 2. The visual window indicates the working status of the SPD: green (normal), red (replace)
- 3. Dual protection of hot melt overcurrent
- 4. Configure telecontrol interface to achieve remote control
03 Technical Parameter Details
| Product name | 48V DC SPD | 500V DC SPD | 600V DC SPD | 800V DC SPD | 1000V DC SPD | 1500V DC SPD |
|---|---|---|---|---|---|---|
| Product model | LKX-PV-48V | LKX-PV-500V | LKX-PV-600V | LKX-PV-800V | LKX-PV-1000V | LKX-PV-1500V |
| In (kA) | 20 | 20 | 20 | 20 | 20 | 20 |
| Imax (kA) | 40 | 40 | 40 | 40 | 40 | 40 |
| Up (kV) | 1.0 | 2.5 | 3.2 | 3.6 | 4.0 | 5.2 |
| Response time (μs) | 25 | 25 | 25 | 25 | 25 | 25 |
| Uc | 48V | 500V | 600V | 800V | 1000V | 1500V |
| Operating temperature | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ |
04 Outer Appearance and Installation Dimensions
05 Installation Considerations
- 1. Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
- 2. It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
- 3. Follow the installation diagram for connection during installation. DC+ is the positive pole, DC- is the negative pole, and PE is the ground wire. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
- 4. After installation, insert the module into place and verify if the surge protection module is functioning correctly.
- 5. During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
- 6. Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions (FAQ)
What does the visual window on the Surge Protective Device (SPD) indicate?
The visual window indicates the working status of the SPD. A green indicator means the device is functioning normally, while a red indicator means the module needs to be replaced.
What voltage ratings are available for this series of DC SPDs?
This product series offers multiple voltage configurations to fit different system requirements, including 48V, 500V, 600V, 800V, 1000V, and 1500V DC options.
What is the response time and discharge capacity of these SPDs?
All models in this series have a response time of 25 microseconds (μs), a nominal discharge current (In) of 20 kA, and a maximum discharge current (Imax) of 40 kA.
What safety precautions must be followed during installation?
Before installing, ensure the power is completely disconnected. Operation while energized is strictly prohibited. It is also recommended to install a fuse or circuit breaker in series at the front end.
How should the DC SPD be wired?
Wiring must strictly follow the installation diagram: connect DC+ to the positive pole, DC- to the negative pole, and PE to the ground wire. Ensure the connections are secure, short, thick, and straight.