China LKX-T1T2-AC 275V AC 3-Pole Surge Protective Device | Factory Direct Suppliers for Industrial Use
LKX-B+C 275V 10kA is for installation at LPZ 0A-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I+II (Class B+C) for various power supply system single-pole protection module. Designed according to IEC 61643-11/EN 61643-11/GB18802.11.
- 10/350, 8/20us varistor; Lightning impulse current to Iimp 10kA.
- Three-poles high discharge capacity surge arrester.
- Consist of varistors and thermal disconnection devices.
- Double terminal for parallel or series (V-shape) connection.
- Multifunctional connection for conductors and busbar.
- Windows will change to red when fault and also provide remote alarm control at the same time.
| Type | LKX-B+C 275V 10kA |
| Rated voltage (max. continuous voltage) [Uc] | 275V AC |
| Lightning impulse current (10/350) [Iimp] | 10kA |
| Nominal discharge current (8/20) [In] | 20kA |
| Max. discharge current (8/20) [Imax] | 40kA |
| Voltage protection level at In [Up] | ≤ 1.5kV |
| Response time [tA] | ≤ 25ns |
| TOV voltage | 335V/5sec |
| Max. back up fuse [L] | 200A gL/gG |
| Max. back up fuse [L-L’] | 125A gL/gG |
| Operating temperature range [Tu] | -40°C...+80°C |
| Cross-sectional area | 35mm² solid / 50mm² flexible |
| Mounting on | 35mm DIN rail |
| Enclosure material | Light grey thermoplastic, UL94-V0 |
| Dimension | 2 mods (36mm) |
| Test standards | IEC 61643-11; EN 61643-11; GB18802.11 |
| Certification | CE (LVD, EMC); ISO |
| Type of remote signalling contact | Switching contact |
| Switching capacity | AC: 250V/0.5A; DC: 250V/0.1A; 150V/0.2A; 750V/0.5A |
| Cross-sectional area for remote signalling contact | Max. 1.5mm² solid / flexible |
| Type | LKX-B+C 275V 10kA |
| Packing unit | 1pc(s) |
275V T1+T2 3P AC Surge Protective Device for 3-Phase Power Systems
This surge protection device is engineered for 3-phase AC power distribution systems and integrates both Type 1 and Type 2 protection in a single unit. It safely discharges direct lightning strikes (10/350 μs waveform) and shields electrical systems from induced or switching surges (8/20 μs waveform). With a continuous operating voltage of 275V AC, it's an ideal choice for main distribution panels in commercial facilities, factories, and other high-risk environments.
Perfect for:This device is designed for installation at the boundary of LPZ 0A-1 or higher. It serves as a modular Class I+II (Class B+C) single-pole surge protection device to safeguard low-voltage equipment from lightning and transient surge damage.
The 10/350 μs waveform represents direct lightning impulse current (Iimp rated at 10kA), while the 8/20 μs waveform represents induced or switching surges (Nominal discharge current In is 20kA and Max discharge current Imax is 40kA).
The device features an inspection window that turns from green to red when a internal fault occurs. Simultaneously, the remote signaling contact provides switching signals to alert operators of the device failure.
It is designed for standard 35mm DIN rail mounting. It supports double terminals for parallel or series (V-shape) connections and is compatible with both conductors and busbars.
The LKX-B+C 275V 10kA SPD complies with IEC 61643-11, EN 61643-11, and GB18802.11 standards, and holds CE (LVD, EMC) and ISO certifications.