China Suppliers Factory Industrial Surge Protective Device 275V AC 3-Pole Type 1+2 SPD 25kA Lightning Protection
LKX-B+C 275V 10kA is for installation at LPZ 0A-1 or higher, protecting low voltage equipment from surge damage. Applied in modular SPD Class I+II (Class B+C) for various power supply system single-pole protection module. Designed according to IEC 61643-11/EN 61643-11/GB18802.11.
- 10/350, 8/20us varistor; Lightning impulse current to Iimp 10kA.
- Three-poles high discharge capacity surge arrester.
- Consist of varistors and thermal disconnection devices.
- Double terminal for parallel or series (V-shape) connection.
- Multifunctional connection for conductors and busbar.
- Windows will change to red when fault and also provide remote alarm control at the same time.
| Type | LKX-B+C 275V 10kA |
| Rated voltage (max. continuous voltage) [Uc] | 275V AC |
| Lightning impulse current (10/350) [Iimp] | 10kA |
| Nominal discharge current (8/20) [In] | 20kA |
| Max. discharge current (8/20) [Imax] | 40kA |
| Voltage protection level at In [Up] | ≤ 1.5kV |
| Response time [tA] | ≤ 25ns |
| TOV voltage | 335V/5sec |
| Max. back up fuse [L] | 200A gL/gG |
| Max. back up fuse [L-L’] | 125A gL/gG |
| Operating temperature range [Tu] | -40°C...+80°C |
| Cross-sectional area | 35mm² solid / 50mm² flexible |
| Mounting on | 35mm DIN rail |
| Enclosure material | Light grey thermoplastic, UL94-V0 |
| Dimension | 2 mods (36mm) |
| Test standards | IEC 61643-11; EN 61643-11; GB18802.11 |
| Certification | CE (LVD, EMC); ISO |
| Type of remote signalling contact | Switching contact |
| Switching capacity | AC:250V/0.5A; DC:250V/0.1A; 150V/0.2A; 750V/0.5A |
| Cross-sectional area for remote signalling contact | Max. 1.5mm² solid / flexible |
| Packing unit | 1pc(s) |
This surge protection device is engineered for 3-phase AC power distribution systems and integrates both Type 1 and Type 2 protection in a single unit. It safely discharges direct lightning strikes (10/350 μs waveform) and shields electrical systems from induced or switching surges (8/20 μs waveform). With a continuous operating voltage of 275V AC, it's an ideal choice for main distribution panels in commercial facilities, factories, and other high-risk environments.
- Three-phase surge protection
- Main switchboard lightning protection
- 275V AC power supply systems
- T1+T2 combined SPD for industrial applications
- High-energy surge protection device for commercial buildings
- DIN rail mounted SPD for distribution boards
- AC surge suppressor for lightning-prone areas
What is the main application of the LKX-B+C 275V 10kA SPD?
This device is designed for installation at the boundary of LPZ 0A-1 or higher. It acts as a Class I+II (Class B+C) combined surge protective device, protecting low-voltage electrical equipment and distribution systems from transient overvoltages and direct lightning strikes.
How does the visual fault indicator window work?
Under normal operating conditions, the status window remains green (or clear). If a fault occurs or the module degrades due to high-energy surges, the window will change to red, indicating that replacement is required. It also triggers the remote alarm signaling contact simultaneously.
What standards does this surge protection device comply with?
The LKX-B+C 275V 10kA is designed, tested, and certified in strict compliance with international standards including IEC 61643-11, EN 61643-11, and the national standard GB18802.11.
Can this device be used for 3-phase AC power systems?
Yes, this combined T1+T2 SPD is designed to protect standard 3-phase AC power distribution systems against both high-energy lightning impulse currents and transient switching surges.
What type of mounting does the unit support?
The unit features a standard DIN rail mounting design compatible with all standard 35mm DIN rails, making it quick and easy to install inside standard distribution boards and switchgear panels.