China Suppliers Factory Type 2 SPD Surge Protection Device 1000V 3-Pole for Photovoltaic & DC Power Systems
Model Meaning
Product Principle and Working Conditions
- Meets Class II (8/20μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20 μs 40kA
- No power frequency continuous flow
- The operating environment temperature is -40°C ~ +80°C
- Remote signaling function is optional
- When product falls, the green window turns to red and remote signaling provides remote alarm function
Technical Parameter Details
| Technical Data | ||||
|---|---|---|---|---|
| POLE | 3P | |||
| SPD Type | Type 2 / Class II | |||
| Technology | MOV / MOV+GDT | |||
| Protection mode(s) | DC+PE, DC-PE | |||
| Max. continuous operating voltage (D.c.) [Ucpv] | 800V | 1000V | 1200V | 1500V |
| Nominal discharge current (8/20μs) [In] | 20kA | |||
| Max. discharge current (8/20μs) [Imax] | 40kA | |||
| Protection level [Up] | ≤3.6kV | ≤4.0kV | ≤4.5kV | ≤5.2kV |
| Response time [tA] | ≤25ns | |||
| Admissible short-circuit current [Isccr] | 25kA | |||
| Max. backup fuse | 125A gL/gG | |||
Mechanical Data
| Mechanical Data | ||||
|---|---|---|---|---|
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DIN rail | |||
| Housing material | Thermoplastic, UL 94 V-0 | |||
| Operating temperature | -40°C ... +80°C | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red Indicator | |||
| Wiring for remote signaling | Optional | |||
| Max. Voltage/Current for remote signaling | Max 1.5mm² solid/flexible | |||
| Standards compliance | 250V/0.1A; 125V/0.2A; 75V/0.5A | |||
| Certification | CE, CB, RoHS, TUV | |||
Outer Appearance and Installation Dimensions
Installation Considerations
- Verify complete power de-energization before commencing installation. Any work on active electrical systems is categorically prohibited.
- For optimal protection, incorporate series-connected overcurrent protection (fuse or breaker) preceding the surge suppression device.
- Installation wiring must strictly comply with the provided schematic: DC+ = Positive terminal, DC- = Negative terminal, PE = Protective earth ground. Ensure proper terminal identification to prevent wiring errors. Post-installation, energize the system by engaging the protective device and confirm proper operational indicators.
- Finalize installation by securing the module in its designated location and performing functional validation of the surge protection system.
- Implement scheduled maintenance inspections including: Visual examination of the diagnostic indicator and verification of alarm contact status. Immediate replacement is mandatory upon detection of red fault indicator illumination or alarm signal activation.
- Parallel surge protection configurations require: True parallel circuit implementation, properly torqued connections, minimum-length conductors, adequate wire gauge (AWG), and direct routing without unnecessary bends.
Frequently Asked Questions (FAQ)
Q1: What is the maximum discharge current (Imax) of this Surge Protective Device?
The maximum discharge current (Imax) for this device is 40kA (8/20μs) using high-quality 34S MOV technology.
Q2: How do the local status indicators work, and what do the colors mean?
The device features a clear visual indicator window. Under normal operating conditions, the window is green. If the device experiences a fault or degradation, the green window turns to red, indicating that immediate replacement is required.
Q3: What mounting standard is required for this SPD?
This surge protective device is designed for easy installation and is compatible with standard 35mm DIN rails.
Q4: Does this device support remote alarm signaling?
Yes, the remote signaling function is optional. When configured, it provides remote alarm capability when the protection module fails.
Q5: What is the operating temperature range for this product?
The device is designed to operate reliably under extreme environmental conditions, with a temperature range of -40°C to +80°C.
Q6: What certifications does this surge protective device hold?
This product is fully compliant with international safety and quality standards, holding CE, CB, RoHS, and TUV certifications.