China Suppliers Factory Type 2 SPD Surge Protection Device 600V 20-40kA for Solar PV and DC Power Systems
Model Meaning
Product Principle and Working Conditions
- Meets Class Ⅱ (8/20μs) SPD tests.
- Based on zinc oxide technology.
- Using 34S MOV, the maximum will be up to 8/20μs 40kA.
- No power frequency continuous flow.
- The operating environment temperature is -40°C ~ +80°C.
- Remote signaling function is optional.
- When the product status falls, the green window turns to red and remote signaling provides a remote alarm function.
Technical Parameter Details
| POLE | 2P/2+0 | ||||
|---|---|---|---|---|---|
| Technology | MOV (Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE / N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max. continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current (8/20μs) [In] | 20kA | 20kA | |||
| Max. discharge current (8/20μs) [Imax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | - | |||
| Temporary overvoltage (TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [Isccr] | 25kA | ||||
| Max. backup fuse | 63AgL/Gg | ||||
Mechanical Data
| Current | AC system | |||
|---|---|---|---|---|
| SPD configuration | Single / Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DIN rail | |||
| Housing material | Thermoplastic, UL 94 V-0 | |||
| Operating temperature | -40°C ... +80°C | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green / Red Indicator | |||
| Wiring for remote signaling | Optional | |||
| Max. Voltage/Current for remote signaling | Max 1.5mm² solid/flexible | |||
| Standards compliance | 250V/0.1A; 125V/0.2A; 75V/0.5A | |||
| Certification | CE, CB, RoHS, TUV | |||
Outer Appearance and Installation Dimensions
Installation Considerations
- Prior to installation, make sure the power supply is turned off. Working on live equipment is strictly forbidden.
- A fuse or circuit breaker should be connected in series upstream of the surge protector for added safety.
- Refer to the wiring diagram for proper installation. Connect DC+ to the positive terminal, DC- to the negative terminal, and PE to the grounding wire. Ensure correct polarity to prevent wiring errors. Once installed, turn on the circuit breaker (or fuse) and verify normal operation.
- Once installed, securely mount the module and confirm that the surge protector is operating as intended.
- Periodically check the surge protector and monitor the fault indicator. A red fault indicator or an alarm signal from the remote terminal means the surge protector has failed and must be repaired or replaced immediately.
- For parallel-connected surge protectors, ensure proper parallel wiring. Use short, thick, straight, and securely fastened cables for optimal performance.
Frequently Asked Questions
Q:What core technology is utilized in this Surge Protective Device?
This Class II SPD is built using advanced zinc oxide technology and features a 34S MOV (Metal Oxide Varistor). It delivers a maximum discharge current (8/20μs) of up to 40kA with no power frequency continuous flow.
Q:What do the visual indicator windows and remote signaling functions indicate?
The device features a local status window. Under normal operating conditions, the window displays green. If the protector fails or falls out of service, the window turns red. Additionally, an optional remote signaling function can trigger a remote alarm for prompt maintenance.
Q:What are the safe operating temperature limits for this SPD?
The device is designed to operate reliably within a wide temperature range, specifically from -40°C to +80°C, making it suitable for diverse industrial and environmental conditions.
Q:What certifications and compliance standards does the product meet?
This surge protective device complies with international safety and performance regulations and has achieved CE, CB, RoHS, and TUV certifications.
Q:What electrical safety precautions must be followed during installation?
Before installation, the power supply must be completely turned off; live installation is strictly prohibited. For adequate safety, a fuse or circuit breaker must be installed in series upstream of the surge protector.
Q:How should wiring polarity and parallel connections be handled?
Ensure proper polarity by connecting DC+ to the positive terminal, DC- to the negative terminal, and PE to the grounding line. For parallel installations, use short, thick, straight, and securely fastened cables to minimize impedance and ensure optimal surge protection performance.