LKX-PV Series Surge Protector (SPD) for Solar and Wind Energy - China Factory Suppliers 500V to 1000V
Model Meaning
Characteristics of the Product
- Plug-in design Surge Protective Device (SPDs)
- The visual window indicates the working status of the SPD: green (normal), red (replace)
- Dual protection of hot melt overcurrent
- Configure telecontrol interface to achieve remote control
Technical Parameter Details
| Product name | 48V DC SPD | 500V DC SPD | 600V DC SPD | 800V DC SPD | 1000V DC SPD | 1500V DC SPD |
|---|---|---|---|---|---|---|
| Product model | LKX-PV-48V | LKX-PV-500V | LKX-PV-600V | LKX-PV-800V | LKX-PV-1000V | LKX-PV-1500V |
| In (kA) | 20 | 20 | 20 | 20 | 20 | 20 |
| Imax (kA) | 40 | 40 | 40 | 40 | 40 | 40 |
| Up (kV) | 1.0 | 2.5 | 3.2 | 3.6 | 4.0 | 5.2 |
| Response time (μs) | 25 | 25 | 25 | 25 | 25 | 25 |
| Uc | 48V | 500V | 600V | 800V | 1000V | 1500V |
| Operating temperature | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ | -40~+85℃ |
Outer Appearance and Installation Dimensions
Installation Considerations
- 1. Safety First: Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
- 2. Circuit Protection: It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
- 3. Wiring Rules: Follow the installation diagram for connection during installation. DC+ is the positive pole, DC- is the negative pole, and PE is the ground wire. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
- 4. Verification: After installation, insert the module into place and verify if the surge protection module is functioning correctly.
- 5. Regular Inspection: During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
- 6. Connection Quality: Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions (FAQ)
What do the green and red indicators mean on the SPD visual window?
The visual status window indicates the working state of the Surge Protective Device. Green represents normal operation, while red indicates that the module has failed and needs to be replaced immediately.
What voltage models are available for this series of DC SPDs?
The LKX-PV series DC Surge Protective Devices are available in several voltage ratings to fit different systems: 48V, 500V, 600V, 800V, 1000V, and 1500V DC.
What is the response time and discharge capacity of these SPDs?
All models in this series feature a rapid response time of less than or equal to 25 microseconds. They have a nominal discharge current (In) of 20 kA and a maximum discharge current (Imax) of 40 kA.
Can the LKX-PV DC SPD be monitored remotely?
Yes, the product is configured with a telecontrol interface to support remote signaling and control, enabling real-time remote system monitoring.
What is the operating temperature range for these surge protectors?
These DC SPDs are designed for extreme environments, with a reliable operating temperature range of -40℃ to +85℃.
What safety precautions should be followed during installation?
Always disconnect the power before installing. Ensure you follow the wiring diagram (DC+ is positive, DC- is negative, PE is ground), use short and thick connection wires in parallel, and install a fuse or circuit breaker in series at the front end.