Single Phase Surge Protective Device LKX-C40 385V 20-40kA from China Suppliers and Factory - Type 2 SPD
Product principle and working conditions
Meets Class Ⅱ (8/20 μs) SPD tests
Based on zinc oxide technology
Using 34S MOV, the maximum will be up to 8/20μs 40ka
No power frequency continuous flow
Compact, yet high surge rated pluggable design, using minimum 35mm DIN rail width
The operating environment temperature is -40℃~+80℃
Red/Green status indication and change-over contacts standard for remote monitoring (Remote function is Option)
Technical parameter details
| Technical Data | |||||
|---|---|---|---|---|---|
| POLE | 2P / 2+0 | ||||
| Technology | MOV (Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE / N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max. continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current (8/20μs) [In] | 20kA | 20kA | |||
| Max. discharge current (8/20μs) [Imax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | - | |||
| Temporary overvoltage (TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [Isccr] | 25kA | ||||
| Max. backup fuse | 63A gL/gG | ||||
Mechanical Data
| Mechanical Data | |
|---|---|
| Current | AC system |
| SPD configuration | Single / Three phase |
| Pluggable | Available |
| Mounting | 35mm DIN rail |
| Housing material | Thermoplastic, UL 94 V-0 |
| Operating temperature | -40℃...+80℃ |
| Protection rating | IP20 |
| Remote Signaling | Green/Red |
| Wiring for remote signaling | Optional (Max 1.5mm² solid/flexible) |
| Max. Voltage/Current for remote signaling | 250V/0.1A; 125V/0.2A; 75V/0.5A |
| Standards compliance | Standards compliant |
| Certification | CE, CB, RoHS, TUV |
Outer appearance and installation dimensions
Installation considerations
Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
Follow the installation diagram for connection during installation. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
After installation, insert the module into place and verify if the surge protection module is functioning correctly.
During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.
Frequently Asked Questions (FAQ)
What surge test class does this device comply with?
This SPD meets Class Ⅱ (8/20 μs) test standards, utilizing high-performance 34S MOV technology to deliver maximum discharge currents up to 40kA.
How do I know if the surge protector is functioning or faulty?
The unit features a visual status window (Green for normal, Red for malfunction). If the window turns red or the optional remote signal sends an alarm, the module needs prompt replacement.
What is the operating temperature range for this SPD?
The device is designed to work reliably in extreme operating environment temperatures ranging from -40℃ to +80℃.
What type of mounting does the device require?
It is designed for standard 35mm DIN rail mounting with a compact, pluggable format for easy maintenance and replacement.
What certifications does this product hold?
The product is certified under CE, CB, RoHS, and TUV standards, ensuring compliance with international electrical safety requirements.
What are the key wiring requirements during installation?
Wiring should be installed in parallel and must remain secure, reliable, short, thick, and straight. A backup fuse or circuit breaker is recommended at the front end.