Type 2 SPD Surge Protection Device 1000V DC 2-Pole for Solar Systems | China Suppliers & Factory
Model Meaning
Product principle and working conditions
Technical parameter details
| POLE | 2P/2+0 | ||||
| Technology | MOV (Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE / N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max. continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current (8/20μs) [In] | 20kA | 20kA | |||
| Max. discharge current (8/20μs) [Imax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | - | |||
| Temporary overvoltage (TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [Isccr] | 25kA | ||||
| Max. backup fuse | 63AgL/gG | ||||
Mechanical Data
| Current | AC system |
| SPD configuration | Single / Three phase |
| Pluggable | Available |
| Mounting | 35mm DIN rail |
| Housing material | Thermoplastic, UL 94 V-0 |
| Operating temperature | -40℃ ... +80℃ |
| Protection rating | IP20 |
| Remote Signaling | Green / Red |
| Wiring for remote signaling | Optional |
| Max. Voltage/Current for remote signaling | Max 1.5mm² solid / flexible |
| Standards compliance | 250V/0.1A; 125V/0.2A; 75V/0.5A |
| Certification | CE, CB, RoHS, TUV |
Outer appearance and installation dimensions
Installation considerations
Prior to mounting, verify that electrical supply is isolated. Working on live equipment is absolutely forbidden.
A protective fuse or breaker should be serially connected upstream of the lightning arrester unit.
Refer to wiring schematics for proper installation. Positive DC connects to DC+, negative to DC-, with PE as earth ground. Prevent reverse polarity. Upon completion, activate the protection device (fuse/breaker) and confirm normal operational indicators.
Post-installation, properly seat the component and validate correct functioning of the overvoltage protector.
Routine maintenance should include visual inspection of the SPD and monitoring of its diagnostic indicator. Either a red warning display or alarm contact activation denotes device failure requiring immediate replacement.
Multi-unit surge suppressors in parallel configuration must maintain true parallel wiring, using minimal-length, large-gauge conductors with secure terminations and straight-line routing.