Model Meaning
Product Principle and Working Conditions
- Meets ClassⅡ (8/20μs) SPD tests
- Based on zinc oxide technology
- Using 34S MOV, the maximum will be up to 8/20μs 40kA
- No power frequency continuous flow
- The operating environment temperature is -40°C~+80°C
- Remote signaling function is optional
- When product falls, the green window turns to red and remote signaling provides remote alarm function
Technical Parameter Details
| POLE | 2P/2+0 | ||||
| Technology | MOV(Metal Oxide Varistors) | GDT | |||
| Protection mode(s) | L-PE/N-PE | NPE | |||
| Nominal voltage (A.C.) [Un] | 220V | 300V | 380V | 400V | 225V |
| Max.continuous operating voltage (D.C.) [Ucpv] | 275V | 320V | 385V | 420V | 225V |
| Nominal discharge current(8/20μs) [In] | 20kA | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | 40kA | |||
| Protection level [Up] | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| Response time [tA] | ≤25ns | ||||
| Temporary overvoltage(TOV) withstand - 5 sec [Ut] | 335V | 440V | 440V | 620V | 335V |
| Admissible short-circuit current [lsccr] | 25kA | ||||
| Max. backup fuse | 63AgL/Gg | ||||
Mechanical Data
| Mechanical Data | |
|---|---|
| Current | AC system |
| SPD configuration | Single/Three phase |
| Pluggable | Available |
| Mounting | 35mm DIN rail |
| Housing material | Thermoplastic, UL 94 V-0 |
| Operating temperature | -40℃...+80℃ |
| Protection rating | IP20 |
| Remote Signaling | Green/Red |
| Wiring for remote signaling | Optional |
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible |
| Standards compliance | 250V/0.1A; 125V/0.2A; 75V/0.5A |
| Certification | CE, CB, RoHS, TUV |
Outer Appearance and Installation Dimensions
Installation Considerations
- 1 Prior to mounting, verify that electrical supply is isolated. Working on live equipment is absolutely forbidden.
- 2 A protective fuse or breaker should be serially connected upstream of the lightning arrester unit.
- 3 Refer to wiring schematics for proper installation. Positive DC connects to DC+, negative to DC-, with PE as earth ground. Prevent reverse polarity. Upon completion, activate the protection device (fuse/breaker) and confirm normal operational indicators.
- 4 Post-installation, properly seat the component and validate correct functioning of the overvoltage protector.
- 5 Routine maintenance should include visual inspection of the SPD and monitoring of its diagnostic indicator. Either a red warning display or alarm contact activation denotes device failure requiring immediate replacement.
- 6 Multi-unit surge suppressors in parallel configuration must maintain true parallel wiring, using minimal-length, large-gauge conductors with secure terminations and straight-line routing.
Frequently Asked Questions (FAQ)
Q1: What is the operating temperature range for this surge protective device (SPD)?
A: The operating environment temperature for this device is designed to function reliably from -40°C to +80°C.
Q2: How does the visual failure indicator work on this SPD?
A: The device features a diagnostic window. Under normal operation, it displays green. If the product falls or fails, the window turns red, and an optional remote signaling function can trigger a remote alarm.
Q3: What core technology is used in this surge protector?
A: This SPD is based on zinc oxide technology utilizing 34S Metal Oxide Varistors (MOV) and Gas Discharge Tubes (GDT) to meet Class II (8/20μs) test standards.
Q4: What mounting method is required for installation?
A: The unit is designed for standard DIN rail mounting on a 35mm DIN rail, making it compatible with standard electrical enclosures.
Q5: What safety precautions must be taken during installation?
A: Before mounting, you must isolate the electrical supply. Working on live equipment is strictly forbidden. Additionally, a protective fuse or breaker must be connected upstream of the unit, and correct wiring polarity must be maintained.
Q6: What certifications does this SPD comply with?
A: The device is fully compliant with international safety and quality standards, holding CE, CB, RoHS, and TUV certifications.