How to Correctly Select a Surge Protective Device (SPD)
How to Correctly Select a Surge Protective Device (SPD)
I. Core Selection Criteria
1. Select SPD Type Based on Protection Level
- Class I SPD (Type 1 Test): Installed at the main distribution panel entrance to withstand direct or induced lightning strikes (discharge current ≥12.5kA, recommended 25kA~100kA). Use hybrid SPDs (GDT + MOV combination) featuring no follow current and low residual voltage.
- Class II SPD (Type 2 Test): Used in sub-distribution panels or equipment room fronts to limit induced overvoltage (discharge current 20kA~40kA). Voltage-limiting MOVs with residual voltage ≤1.5kV are typical.
- Class III SPD (Type 3 Test): Installed near terminal equipment (e.g., servers, switches) to protect sensitive devices (discharge current 10kA~20kA), with residual voltage ≤1.2kV.
2. Match System Parameters
- Maximum Continuous Operating Voltage (Uc): Must be ≥1.15 times the system nominal voltage (e.g., select Uc ≥440V for a 380V system) to avoid false triggering due to voltage fluctuations.
- Voltage Protection Level (Up): Class I SPD: Up ≤2.5kV
Class II SPD: Up ≤1.5kV
Class III SPD: Up ≤1.2kV Ensure Up ≤80% of the equipment’s withstand voltage.
- Response Time:
Class I SPD: ≤25ns
Class II SPD: ≤25ns
Class III SPD: ≤1ns
3. Grounding and Installation Requirements
- Grounding Resistance: ≤4Ω (≤10Ω in high soil resistivity areas), with grounding conductor cross-section ≥25mm².
- Installation Location: Prioritize proximity to protected equipment, minimizing lead length (total lead length ≤0.5m) to avoid induced voltage stacking.
II. Key Considerations
1. SPD Type Selection
- Voltage-Switching SPD (GDT): High discharge current (≥100kA) but risks follow current and power interruption; suitable only for Class I protection.
- Voltage-Limiting SPD ( MOV): Low residual voltage but prone to aging; requires regular monitoring.
- Hybrid SPD: Combines advantages of switching and limiting types; recommended for multi-stage protection systems.
2. Inter-Stage Coordination
- Minimum spacing between upper and lower SPDs: ≥10m (switching + limiting) or ≥5m (limiting + limiting); otherwise, install decoupling devices.
- Energy coordination formula: Upper SPD absorbs 80% of energy, lower SPD absorbs 20%.
3. Backup Protection
- Series-connected circuit breakers or fuses (rated current ≥1.5 times SPD continuous current) to prevent short-circuit escalation.
- Select SPDs with degradation indicators for automatic disconnection and alarm upon failure.
4. Special Scenario Requirements
- TN-C System: Use 3+NPE or 3P+N mode to avoid PEN line re-grounding risks.
- TT System: Install SPD between N and PE lines to prevent potential difference backflash.
III. Design Verification Testing
1. Lightning Surge Test: Verify SPD withstand capability under 10/350μs waveform (Class I) or residual voltage under 8/20μs waveform (Class II/III).
2. Thermal Stability Test: Continuous current flow for 2 hours (50% of Imax), checking temperature rise ≤60K.
3. Degradation Monitoring: Use built-in sensors to monitor leakage current (normal value <10μA); trigger alarms if exceeded.
IV. Common Mistakes and Solutions
Mistake 1: Ignoring system grounding type, causing SPD failure.
Solution: For TN systems, select 3P+N; for TT systems, select 3P+PE; for IT systems, select 3P.
Mistake 2: Insufficient SPD spacing, leading to inter-stage interference.
Solution: Maintain ≥10m between upper/lower SPDs or install decoupling inductors (≥1mH).
Mistake 3: Neglecting backup protection, risking fire after SPD short-circuit.
Solution: Series-connected fuses (rated current ≥1.5 times SPD continuous current).
Summary
SPD selection requires comprehensive evaluation of system voltage, lightning risk, equipment withstand capability, and installation environment. Class I SPDs prioritize discharge capacity, while Class II/III focus on residual voltage control. Signal SPDs must match interface types. Regular inspections (e.g., leakage current, physical aging) ensure long-term protection efficacy.









