1500V 3P T2 Surge protection device for air conditioner | LKX-PV
01
Model Meaning

02
Product principle and working conditions
1.Meets ClassⅡ (8/20μs) SPD tests
2. Based on zinc oxide technology
3. Using 34S MOV, the maximum will be up to 8/20μs 40kA
4. No power frequency continuous flow
5.The operating environment temperature is -40°C~+80°C
6. Remote signaling function is optional.
7. When product falls, the green window turns to red and remote signaling provides remote alarm function
03
Technical parameter details
| Technical Data | ||||
| POLE | 3P | |||
| SPD Type | Type 2/ClassⅡ | |||
| Technology | MOV/MOV+GDT | |||
| Protection mode(s) | DC+PE.DC | |||
| Max.continuous operating voltage (D.c.) [Ucpv] | 800V | 1000V | 1200V | 1500V |
| Nominal discharge current(8/20μs) [In] | 20kA | |||
| Max.discharge current (8/20μs) [lmax] | 40kA | |||
| Protection level [Up] | ≤3.6kV | ≤4.0kV | ≤4.5kV | ≤5.2kV |
| Response time [tA] | ≤25ns | |||
| Admissible short-circuit current [lsccr] | 25kA | |||
| Max, backup fuse | 125AgL/Gg | |||
04
Mechanical Data
| Mechanical Data | ||||
| Current | AC system | |||
| SPD configuration | Single/Three phase | |||
| Pluggable | Available | |||
| Mounting | 35mm DlN rail | |||
| Housing material | Thermoplastic,UL 94 V-O | |||
| Operating temperature | -40℃...+80℃ | |||
| Protection rating | IP20 | |||
| Remote Signaling | Green/Red | |||
| Wiring for remote signaling | Optional | |||
| Max.Voltage/Current for remote signaling | Max 1.5mm solid/flexible | |||
| Standards compliance | 250V/0.1A;125V/0.2A;75V/0.5A | |||
| Certification | CE,CB,RoHS,TUV | |||
04

Outer appearance and installation dimensions


05
Installation considerations
1.Before installation, ensure power is disconnected. Operating while energized is strictly prohibited.
2.It is recommended to install a fuse or circuit breaker in series at the front end of the surge protection module.
3.Follow the installation diagram for connection during installation. DC+ is the positive pole, DC- is the negative pole, and PE is the ground wire. Avoid incorrect connections. After installation, close the circuit breaker (or fuse) switch and check if the operation status is normal.
4.After installation, insert the module into place and verify if the surge protection module is functioning correctly.
5.During use, regularly inspect the surge protection module and check the status of the fault display window. If the fault display window turns red or if the remote signaling terminal outputs an alarm signal, it indicates a malfunction of the surge protection module, which should be promptly repaired or replaced.
6.Parallel-connected power surge protection modules should be installed in parallel. The connection wires must be secure, reliable, short, thick, and straight.